+86-0755-29833888(Shenzhen) +86-0750-2933888(Kaiping)Address:Renda Science and Technology Park, Shiyan Street, Bao'an District, Shenzhen, Guangdong Province
RDE1KS-48-1U communication lithium battery UPS is a new generation of special power supply products designed for uninterrupted AC power supply systems such as communication base stations and mail and motor rooms. Using advanced DSP digital control technology and high-frequency switching technology, in addition to having double conversion online, zero conversion, fault bypass and other functions, unattended function is added, and it can be matched with new lithium iron phosphate batteries.
◆ Lithium battery energy storage: The latest iron lithium battery can be configured as the energy storage device of UPS. As a representative of new energy, lithium iron batteries have a small volume (1/3 of ordinary lead-acid batteries), long life, good high temperature performance, and easy to meet the requirements of fast replay points.
◆ Unattended function: suitable for remote, large or unmanned sites. (Customized).
◆ High-current charging and management system, which can adapt to lithium iron phosphate batteries and ordinary lead-acid batteries.
◆ Fully adopt DSP digital control technology, the product is more stable and the quality is superior.
◆ The load power factor is 0.8, and the load capacity is stronger.
◆ Active input power factor correction (PFC) is as high as 0.98 or more, avoiding pollution to the power grid environment and meeting the social requirements of energy conservation and environmental protection.
◆ Wide input voltage frequency range can supply power normally even in remote areas with very harsh power environment, reducing the number of battery discharges and improving the service life of the battery.
◆ When the zero switching mains power is unstable, the conversion time of the UPS power supply mode is zero, which effectively ensures the safety and reliability of load operation.
◆ Convenient remote monitoring function, providing standard RS232 interface, optional dry contact, RS485, and network monitoring card.
Model
Properties and parameters
|
RDE1KS-48-1U
|
|
Rated output capacity
|
1KVA/800W
|
|
Working mode
|
Double conversion online
|
|
Communication
Enter
|
Rated voltage
|
220Vac
|
Rated frequency
|
50Hz/60Hz
|
|
Input voltage range
|
(172~268)±7Vac
|
|
Input frequency range
|
(45~55)±0.5Hz
|
|
AC input harmonics
|
<3%.
|
|
DC input
|
DC rated voltage
|
48V
|
Low voltage alarm/protection point
|
42/40-64V
|
|
Charging function
|
Charging voltage
|
57V
|
Charging function
|
5-7A (external battery).
|
|
AC output
|
Output voltage
|
220Vac±3% (inverter output).
|
Output frequency
|
50±5Hz (when AC input is normal), 50Hz±1% (when AC input is abnormal).
|
|
Dynamic voltage transients
|
<5%.
|
|
Dynamic transient recovery time
|
< 60ms
|
|
Waveform
|
Sine wave THD <3% (linear load); THD <8% (nonlinear load).
|
|
Output power factor
|
0.8
|
|
Overload capacity
|
In mains mode, 130% lasts for not less than 20s
Battery mode
|
|
Output current peak factor
|
3:1
|
|
Direct AC conversion time
|
0ms
|
|
Inverter bypass transition time
|
<4ms
|
|
Communication functions
|
Standard RS232+ smart slot, smart slot expandable RS485, dry node, SNMP and other monitoring functions.
|
|
Protection features
|
DC input overvoltage, undervoltage protection, overload protection,
overtemperature protection, short circuit protection, output overvoltage, low voltage protection
|
|
Weight Kg
|
5.5
|
|
SIZE (W*H*D) MM
|
432*88*300
|
|
Installation method
|
Rack-mounted and wall-mounted
|