RDH series special UPS (special inverter power supply) is a special power supply product designed for uninterrupted AC power supply systems such as power plants, substations, distribution stations, post and telecommunications, railways, etc., with double conversion online, zero conversion and fault bypass functions. This series of products is using advanced DSP digital control technology, high-frequency switching technology, so that the series of products better quality, better performance, easier to install and maintain.
RDH series special UPS (special inverter power supply) is a special power supply product designed for uninterrupted AC power supply systems such as power plants, substations, distribution stations, post and telecommunications, railways, etc.
◆ Fully adopt DSP digital control technology, the product is more stable and the quality is superior.
◆ DC self-start function, in DC mode, DC voltage out of range, dedicated UPS turn off the output, when it returns to normal value, dedicated UPS automatically boots.
◆ The load power factor is 0.8, which is designed according to the latest electrical equipment standards.
◆ Active input power factor correction (PFC) is as high as 0.98 or more, avoiding pollution to the power grid environment and meeting the social requirements of energy conservation and environmental protection.
◆ Wide input voltage frequency range can supply power normally even in remote areas with very harsh power environment, reducing the number of battery discharges and improving the service life of the battery.
◆ When the zero switching mains power is unstable, the conversion time of the UPS power supply mode is zero, which effectively ensures the safety and reliability of load operation.
◆ Convenient remote monitoring function, providing standard RS232 interface, optional dry contact, RS485, and network monitoring card.
Product Model
Properties and parameters
|
RDH1K-48/100/220
|
RDH2K-48/100/220
|
RDH3K-48/100/220
|
||||||||
Rated output capacity
|
1000VA/800W
|
2000VA/1600W
|
3000VA/2400W
|
||||||||
Communication
Enter
|
Rated voltage
|
220Vac/230Vac/240Vac
|
|||||||||
Rated frequency
|
50Hz/60Hz
|
||||||||||
Input voltage range
|
(172~268)±7Vac
|
||||||||||
Input frequency range
|
(45~55)±0.5Hz
|
||||||||||
AC input harmonics
|
<3%.
|
||||||||||
Charge
|
Charging current
|
5-7A (charging function, optional function).
|
|||||||||
DC
Enter
|
DC rated voltage
|
48Vdc/110Vdc/220Vdc
|
|||||||||
48V
Communication systems
|
Rated current
|
19.6A
|
39.2A
|
58.8A
|
|||||||
DC voltage range
|
40-58V
|
||||||||||
Enter the low voltage alarm/protection point
|
40/42V
|
||||||||||
Enter the high voltage alarm/protection point
|
58/58V
|
||||||||||
110V
Power system
|
Rated current
|
8.6
|
17.2
|
25.8
|
|||||||
DC voltage range
|
90-130V
|
||||||||||
Enter the low voltage alarm/protection point
|
95/90V
|
||||||||||
Enter the high voltage alarm/protection point
|
130/130V
|
||||||||||
220V
Power system
|
Rated current
|
4.3
|
8.6
|
12.9
|
|||||||
DC voltage range
|
180-260V
|
||||||||||
Enter the low voltage alarm/protection point
|
190/180V
|
||||||||||
Enter the high voltage alarm/protection point
|
260/260V
|
||||||||||
Exchange Output
|
Output voltage
|
220Vac±3% (inverter output).
|
|||||||||
Output frequency
|
50±5Hz (when AC input is normal), 50Hz±1% (when AC input is abnormal).
|
||||||||||
Dynamic voltage transients
|
<5%.
|
||||||||||
Dynamic transient recovery time
|
< 60ms
|
||||||||||
Waveform
|
Sine wave THD <3% (linear load); THD <8% (nonlinear load).
|
||||||||||
Output power factor
|
0.8
|
||||||||||
Overload capacity
|
130% for not less than 20s
|
||||||||||
Output current peak factor
|
3:1
|
||||||||||
DC and AC conversion time
|
0ms
|
||||||||||
How the panel is displayed
|
LCD/LED optional
|
||||||||||
Communication functions
|
Standard RS232+ smart slot, smart slot expandable RS485, dry node, SNMP and other monitoring functions.
|
||||||||||
Protection features
|
DC input overvoltage, undervoltage protection, overload protection,
overtemperature protection, short circuit protection, output overvoltage, low voltage protection
|
||||||||||
SIZE (W*H*D) MM
|
432*88*300
|
432*88*440
|
|||||||||
Weight Kg
|
6.5
|
9.5
|
10
|