10~80KVA series three-phase high-frequency medium-power UPS adopts pure online double conversion structure and advanced DSP control technology, with the use of high-power device IGBT and SCR, on the basis of stable, advanced and efficient digital/analog hybrid technology, a large-capacity sine wave online high-intelligence UPS integrating digitalization, informatization and networking is designed.
Renda high-frequency online UPS power supply 10~80KVA series, used in areas with a good power environment, common use places are: small and medium-sized data centers for enterprises, network management centers, enterprise server rooms, etc.
● extremely strong load adaptability
●Wide input voltage range, can connect to various generators
●Mature power frequency online double conversion provides extremely high reliability
● Perfect charging management
●Large screen Chinese display, perfect communication interface
●Output isolation transformer is resistant to shock and isolates grid interference
● DC start
●Automatic restart of incoming calls (battery empty).
●ECO operating mode efficiency is up to 95%.
Randa high-frequency online UPS power supply 10-80KVA (technical indicators). | |||||||
models | RDHI3310 | RDHI3315 | RDHI3320 | RDHI3330 | RDHI3340 | RDHI3360 | RDHI3380 |
capacity | 10KVA | 15KVA | 20KVA | 30KVA | 40KVA | 60KVA | 80KVA |
main input | |||||||
input voltage | 380V/400V/415V (line voltage), 50/60Hz | ||||||
input mode | 3Pn+N+PE | ||||||
power factor | >0.99 | ||||||
current distortion rate | THDi<3% | ||||||
voltage range | +25%~-40% | ||||||
-20%~-40%, with a load capacity of 100% and 70% linear derating | |||||||
frequency range | 40-70HZ | ||||||
bypass input | |||||||
input voltage | 380V/400V/415V | ||||||
voltage range | -20% ~ +15% | ||||||
frequency range | ±3Hz (settable ±15%) | ||||||
output | |||||||
voltage accuracy | ±1% | ||||||
dynamic voltage transients | 5%(0~100% load change). | ||||||
voltage distortion rate | THD<1% (linear load), THD<3% (nonlinear load). | ||||||
power factor | 0.9 | ||||||
frequency tracking range | 50/60Hz±3Hz, (settable ±15%) | ||||||
frequency accuracy | ±0.01% | ||||||
three-phase phase accuracy | 120°±0.5° | ||||||
voltage imbalance (100% unbalanced load). |
±3% | ||||||
frequency tracking rate | 0.5Hz/s to 5Hz/s , (configurable). | ||||||
peak ratio | 3:01 | ||||||
overload capacity | 105%, long-term work | ||||||
110%, turn bypass after 1 hour | |||||||
125%, turn to bypass after 10 minutes | |||||||
150%, turn to bypass after 1 minute | |||||||
>150%, turn to bypass after 200ms | |||||||
bypass overload capacity | 135%, long-term work | ||||||
135% ~ 150%, 6 minutes | |||||||
load >180%, working time longer than 100ms | |||||||
system | |||||||
system efficiency | normal mode: 95%. | ||||||
economic model: 98%. | |||||||
battery mode efficiency | 95% | ||||||
battery configuration | 12V, 40 knots (32~44 knots can be set). | ||||||
display | LCD + LED + keyboard | ||||||
EMI | IEC62040-2 | ||||||
insulation resistance | >2M (500VDC) | ||||||
dielectric strength | (input and output to ground) 2820Vdc, leakage current less than 3.5mA, no arcing for 1 minute | ||||||
surge protection | meet the requirements of class IV installation position specified in IEC60664-1, that is, the ability to withstand 1.2/50us+8/20us mixed wave is not less than 6KV/3KA | ||||||
protection level | IP20 | ||||||
communication interface | RS232, RS485, dry contact, SNMP card, EPO, generator interface | ||||||
wiring method | supports up and down lines | ||||||
operating temperature | 0-40℃ | ||||||
relative humidity | 0-95% (non-condensing). | ||||||
noise (dB). | <55dB | ||||||
weight (KG). | 43 | 46 | 46 | 60 | 93 | 150 | 150 |
size (W*D*H)(mm). | 280*731*668 | 320*781*788 | 540*764*1100 | 600*850*1350 |